DEC 7000 ~~~~~~~~ Configuring Environment *********************** Environment Physical Characteristics Power ---------------------------------------------------------------------------- Environmental ================================================= Environment Operating Non Operating Temperature 15 to 28C (59 to 82F) -40 to 66C (-40 to 151F) Humidity 20% to 80% 10% to 95% Altitude 0-2.4 km (0-8000 ft) 9,100 m (30,000 ft) Vibration 2-22 Hz @ 0.01"da minimum 22-500 Hz @ 0.25g max. Heat Fully configured system (system cabinet) dissipation 17,700 Btu/hr, 5,200 W Note:1 Fully configured system (system cabinet with two I/O expansion cabinets) 37,500 Btu/hr, 11,020 W Minimally configured system (system cabinet) 3,400 Btu/hr, 1,000 W Note:2 Note:1 The power system provides unity power factor which allows full utilization of the input line current (Watts = VA). Approximate Btus for a given system configuration can be calculated by multiplying the "EPU" value per cabinet by 85.4. Note:2 Minimally configured system contains one regulator, one CPU module, one memory module, one IOP module, and one Ethernet controller.
Physical Characteristics ======================== Physical Characteristics Operating Shipping Height 170.0 cm (67.0 in.) 195.0 cm (76.7 in.) Width (per cabinet) 80. cm (31.5 in.) 106.0 cm (41.7 in.) Depth 87.5 cm (34.4 in.) 119.0 cm (46.8 in.) Weight, full configuration Without batteries 408 kg (900 lb) 545 kg (1200 lb) With batteries 448 kg (1000 lb) 585 kg (1300 lb) Clearances Operating Service Front 1.0 m (40 in.) 1.0 m (40 in.) Rear 1.5 m (59 in.) 1.0 m (40 in.) Sides 0 0
Power ===== Parameter US - Europe - Japan Canada GIA Nominal voltage 120/208 V 380-415 V 202 V Frequency range 50-60 Hz on all systems Phases 3-phase star 4-wire mid-GND or 4-wire N-GND 3-wire junction GND Max. input/phase 24 A rms 12.8 A rms 24 A rms Surge current 50A peak Uninterruptible power Standard on 10000 systems system/battery backup Optional on 7000 systems Built-in power conditioning Standard on all systems N+1 power Standard on 10000 systems Optional on 7000 systems Receptacle
----------------------------------------------------------------------------
| |