Product Details

DEC 7000 / 10000 -
DEC 7000
~~~~~~~~
Configuring Environment
***********************
Environment
Physical Characteristics
Power
----------------------------------------------------------------------------
Environmental
=================================================
Environment Operating Non Operating
Temperature 15 to 28C (59 to 82F) -40 to 66C
(-40 to 151F)
Humidity 20% to 80% 10% to 95%
Altitude 0-2.4 km (0-8000 ft) 9,100 m (30,000
ft)
Vibration 2-22 Hz @ 0.01"da minimum 22-500 Hz @ 0.25g
max.
Heat Fully configured system (system cabinet)
dissipation 17,700 Btu/hr, 5,200 W
Note:1
Fully configured system (system cabinet with
two I/O expansion cabinets) 37,500 Btu/hr,
11,020 W
Minimally configured system (system cabinet)
3,400 Btu/hr, 1,000 W Note:2
Note:1 The power system provides unity power factor which allows full
utilization of the input line current (Watts = VA). Approximate Btus for a
given system configuration can be calculated by multiplying the "EPU"
value per cabinet by 85.4.
Note:2 Minimally configured system contains one regulator, one CPU module,
one memory module, one IOP module, and one Ethernet controller.

Physical Characteristics
========================
Physical Characteristics Operating Shipping
Height 170.0 cm (67.0 in.) 195.0 cm (76.7 in.)
Width (per cabinet) 80. cm (31.5 in.) 106.0 cm (41.7 in.)
Depth 87.5 cm (34.4 in.) 119.0 cm (46.8 in.)
Weight, full configuration
Without batteries 408 kg (900 lb) 545 kg (1200 lb)
With batteries 448 kg (1000 lb) 585 kg (1300 lb)
Clearances Operating Service
Front 1.0 m (40 in.) 1.0 m (40 in.)
Rear 1.5 m (59 in.) 1.0 m (40 in.)
Sides 0 0

Power
=====
Parameter US - Europe - Japan
Canada GIA
Nominal voltage 120/208 V 380-415 V 202 V
Frequency range 50-60 Hz on all systems
Phases 3-phase star 4-wire mid-GND or
4-wire N-GND 3-wire junction
GND
Max. input/phase 24 A rms 12.8 A rms 24 A rms
Surge current 50A peak
Uninterruptible power Standard on 10000 systems
system/battery backup Optional on 7000 systems
Built-in power conditioning Standard on all systems
N+1 power Standard on 10000 systems
Optional on 7000 systems
Receptacle

----------------------------------------------------------------------------
Page 1 - Page 2 -