Product Details

*AlphaServer 2100A * -
AlphaServer 2100A
~~~~~~~~~~~~~~~~~
Configuring Environment
***********************
Physical Characteristics
Environmental
Electrical
Regulatory
----------------------------------------------------------------------------
Physical Characteristics
========================
Shipping Dimension Installed Dimension
Height 119 cm (46.9 in.) 70 cm (27.6 in.)
Width* 102 cm (40.0 in.) 43 cm (16.9 in.)
Depth* 61 cm (24.0 in.) 81 cm (31.9 in.)
Weight 85 kg (187 lb) typical 85 kg (187 lb) typical
114 kg (250 lb) maximum 114 kg (250 lb) maximum
Clearances
Operating Service
Front 75 cm (29.5 in.) 75 cm (29.5 in.)
Rear 15.2 cm (6 in.) 76.2 cm (30 in.)
Sides none 76.2 cm (30 in.)

Environmental
=============
Temperature Relative Humidity
Operating 10-35 C (50-95 F)** 20-80%
Non operating 20-80%
Storage(60 -40-66 C (-40-151 F) 10-95%
days)
Rate of 11 C/hr (20 F/hr) 20%/hr
change
Maximum Wet Bulb Temperature Minimum Dew Point Temperature
Operating 28 C (82 F) 2 C (36 F)
Storage 46 C (115F) Not tested
(60 days)
Maximum Heat Dissipation
Current 800 Watt, 3005 Btu/hr (single supply)
1280 Watt, 4371 Btu/hr (dual supply)
Theoretical 920 Watt, 3142 Btu/hr (single supply)
1675 Watt, 5720 Btu/hr (dual supply)
Air Flow and Quality
Intake Front
location
Exhaust Rear
location
Altitude Mechanical Shock
Operating 2000 m (6562 ft) 7.5 G 10 ms
Non operating 3600 m (12,000 ft) 20 G peak 30 ms
Vibration Acoustics
Operating 10-500 Hz .1 G peak LNPEc (Bels)
6.6 maximum per ISO 7779

Electrical
==========
Nominal ac voltage 100-120 Vac 220-240 Vac
Voltage range (Vac) 88-132 Vac 180-264 Vac
Power source phase Single Single
Nominal frequency (Hz) 60 Hz 50 Hz
Frequency Range(Hz) 47-63 Hz 47-63 Hz
Maximum inrush current 50 Amps 50 Amps
RMS current at nominal 8.5 Amps 4.0 Amps
voltage (steady state)
Power cord Type IEC 320 C16
Length 240 cm (113 in.)
U.S. plug NEMA 5-15, Socket EIC
320 Sheet, C-15

Regulatory
==========
Agency Approvals Reviewed To
UL Listed to UL1950 (2nd edition) AS 3260 Australian Standard
CSA Certified to CAN/ C22.2 No. 950-M89 SS 436 14 50 Swedish Standard
TUV EN 60950 VDE 0805 Gsmarked ZH1/618 NZS 6661:1989 New Zealand Standard
FCC 15J Part 15 (Class B) Verified EN 60 950: 1992 European Norm
CE Class B Verified IEC 950 (2nd edition)
VCCI Class II ITE

* Dimensions of shipping pallet; fork-lift access is on the width dimension
** Maximum operating temperature at Sea Level. Reduce by 1 C (1.8 F) for
each 600 m (2000 ft) above Sea Level.
Higher altitudes are possible if maximum operating temperature is reduced
(see Temperature, above); other restrictions may apply, such as maximum
permissible altitude for hard drives. _Top of page_
----------------------------------------------------------------------------